2253 S SPRINGFIELD AVE
ESC: NEEDED - CORROSIAN ON MAST AND METER SOCKET PRE-ESC: ALLOWED BFEED REQ'D: 40A METER/SERVICE: UNIT 1 METER#270128152 TRIPLE SOCKET/OVERHEAD - CUSTOMERS IS THE MIDDLE PANEL: CUSTOMERS IS LABELED "1ST FLOOR" 125/ RECOMMENDED INTERCON: SUPPLY TAP IN THE MAIN SERVICE PANEL SCOPE REPLACE TRIPLE METER SOCKET WITH A CONED APPROVED 100A TRIPLE METER SOCKET AND PANS REPLACE THE PART OF THE MAST THAT IS RUSTY ENSURE BONDING AND GROUNDING ARE UP TO CODE. BOND THE COLD WATER MAIN. AHJ CHICAGO GOVERNING ELECTRICAL CODE 2018 CHICAGO ELECTRICAL CODE