Chicago · permit B100912622
3207 S CANAL ST
ESC: NEEDED METER LOCATION AND TANDEM BREAKERS IN MSP PRE-ESC: BFEED REQ'D: 20A & 40A RECOMMENDED INTERCON: SUPPLY TAP IN THE METER CAN _______________ METER/SERVICE: SOCKET/OVERHEAD CLEARANCE - OVER STAIRS PANEL: 200/200A TANDEM BREAKERS _______________ SCOPE MOVE METER SOCKET TO A CODE COMPLIANT/COMED APPROVED LOCATION. ADD A SUB PANEL FED FROM THE MAIN SERVICE PANEL. DIVERT BRANCH CIRCUITS TO ELIMINATE TANDEM BREAKERS IN THE MAIN. AHJ: CHICAGO GOVERNING ELECTRICAL CODE: 2018 CHICAGO ELECTRICAL CODE CHECK AND FOLLOW AHJ AMENDMENTS PRIOR TO PERMIT ENSURE BONDING AND GROUNDING ARE UP TO CODE. BOND THE COLD WATER MAIN. BOND STREET SIDE FIRST
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2021-03-15
- Issued
- 2021-03-15
- Time to issue
- same day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- VIVINT SOLAR DEVELOPER,LLC,
Chicago details
- Review type
- EXPRESS PERMIT PROGRAM
- Milestone
- COMPLETE
- Community area (code)
- 60