Chicago · permit B101044680
7644 S HOYNE AVE
1) OCPD AND CIRCUIT CONDUCTOR NOT MATCHING.. NEC TABLE 210.24, CORRECTED 2)NEC 110.2(A) , INSTALLED 1" KO SEAL IN MSP. 3) TIGHTENED LOOSE FITTINGS 4)WIRE MANAGEMENT 5) GROUNDING AND BONDING OG PV AND SERVICE SYTEMS 6) REMOVED BONDING FROM NEUTRAL LUG IN AC DISCONNECT 7) REPLACED 1/2" CONNECTOR W/LOCKNUT 8. PATCH WORK NEEDS TO BE DONE. HOLE IN HOUSE NOT PROPERLY SEALED. NEED TO USE DUCT SEAL, INSTEAD OF FOAM, SEALING UP THE ELECTRICAL HOLES WHERE FOAM IS AND WHERE THERE¿S A GAP IN THE CIRCUIT BREAKER BOX.