Chicago · permit B101037362
3240 S MORGAN ST
**ELECTRICAL ONLY PERMIT**UPGRADE ELECTRICAL SERVICE FROM 200 AMPS TO 800 AMPS.- REMOVE EXISTING RAISER. - INSTALL (2) NEW PARALLEL 3¿ RIGID CONDUIT RAISERS UP TO COM ED ATTACHMENT. - INSTALL (2) NEW 3¿ SERVICE HEAD. - WIRE PARALLEL RAISERS WITH 500 MCM THHN COPPER WIRE. - INSTALL NEW SERVICE ATTACHMENT MINIMUM OF 18 IN. BEYOND THE SERVICE HEAD TO MAKE CONNECTIONS TO SERVICE DROP WIRES. - PROPERLY SECURE 3¿ RIGID CONDUIT RISER TO STRUCTURE OF BUILDING. - INSTALL NEW 800 AMP TAP BOX. - INSTALL AN 8'X 5/8¿ SUPPLEMENTAL COPPER GROUND ROD WITH CONNECTIONS AT METER FITTING WITH #6 THHN COPPER WIRE. - INSTALL (2) 3 GANG METER MODULES CONSISTING OF (5) METERS WITH 100 AMP MAIN BREAKER DISCONNECTS AND (1) 200 AMP MAIN BREAKER DISCONNECT. - TEMPORARY RECONNECT POWER TO EXISTING SERVICE DROP. - INSTALL DUCT SEAL IN SERVICE ENTRANCE CONDUIT. - REWIRE EXISTING ELECTRICAL PANELS WITH 3 AWG THHN COPPER WIRE TO NEW METER DISCONNECTS. - EXISTING ELECTRICAL PANELS TO REMAIN. - GROUND ELECTRICAL S
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2023-10-31
- Issued
- 2023-11-09
- Time to issue
- 9 days
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- ESSENTIAL LIGHTING INC
Chicago details
- Review type
- EXPRESS PERMIT PROGRAM
- Milestone
- COMPLETE
- Community area (code)