Chicago · permit B101011866
7417 N TALMAN AVE
EV WALL CONNECTOR 1. FURNISH AND INSTALL (1) 60 AMP, 240 VOLT, 3 WIRE DEDICATED CIRCUIT. 2. PROPOSAL INCLUDES RUNNING (1) 3/4" RIGID EMT CONDUIT INSTALLED FROM THE EXISTING 200 AMP PANEL TO THE GARAGE. CONDUIT WILL BE SURFACE MOUNTED IN THE GARAGE. 3. CIRCUITRY WILL CONSIST OF (2) #6AWG THHN COPPER CONDUCTORS AND (1) #10 AWG THHN GROUNDING CONDUCTOR. 4. INSTALL (1) CUSTOMER FURNISHED EV WALL CHARGER. WALL CONNECTOR WILL BE LOCATED ON THE NORTH GARAGE WALL, CLOSER TO THE BAY DOOR. 5. CHARGER WILL DELIVER UP TO 48 AMPS. 6. FURNISH AND INSTALL (1) DISCONNECT SWITCH AS REQUIRED BY CODE. DISCONNECT SWITCH WILL BE INSTALLED NEXT TO THE WALL CONNECTOR. 7. FURNISH AND INSTALL (1) 60 AMP 2 POLE BREAKER IN THE MAIN PANEL TO FEED THE WALL CONNECTOR. 8. PROVIDE (1) LOAD CALCULATION FOR THE HOUSE INCLUDING THE NEW EV CHARGER 9. PROPOSAL INCLUDES TRENCHING AND BACKFILLING. LANDSCAPE RESTORATION IS NOT INCLUDED. 10. PROPOSAL INCLUDES SIDEWALK REMOVAL AS NECESSARY. CONCRETE RESTORATION IS NOT INC
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2023-04-06
- Issued
- 2023-04-07
- Time to issue
- 1 day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- REIN ELECTRIC, INC.
Chicago details
- Review type
- EXPRESS PERMIT PROGRAM
- Milestone
- COMPLETE
- Community area (code)
- 2