Chicago · permit B100941087
11012 S AVENUE B
TRENCH HAS TO BE REDONE TO MEET AHJ STANDARDS. REMOVE CONDUCTORS AND CONDUIT FROM TRENCH RUN PRIOR TO TRENCHING. POST TRENCHING RE-PIPE AND PULL NEW CONDUCTORS IN TRENCH AND RECONNECT PV EQUIPMENT TO ENSURE WORKING PV SYSTEM. BEFORE TRENCHING OR BORING CONTACT JULIE TO HAVE THE TRENCH PATH MARKED FOR ANY UTILITIES. SEE PHOTOS FOR TRENCH PATH. DIG A TRENCH APPROX 40 FEET MINIMUM 18 INCHES DEEP TO THE TOP OF THE CONDUIT. INSTALL 1 INCH SCHED 80 PVC AND ADAPTORS WITH RMC 90'S AND STUB UPS ON BOTH ENDS. LEAVE A PULL STRING IN THE CONDUIT AND PUT TAPE OVER THE OPEN COUPLINGS SO WATER CANNOT ENTER.
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE