SYSTEM IS DESIGNED FOR 20 PANELS WITH A 7.6KW AC INVERTER. METER CAN IS 120AMP WILL NOT ACCOMMODATE BACKFEED, RISER WILL NEED TO BE REPLACED TO ACCOMMODATE INCREASED SERVICE WIRE SIZE, MAIN SERVICE PANEL (MSP) REFLECTS CLOTH SERVICE FEEDERS THAT ARE DOUBLE TAPPED AND BY PASS THE MAIN TO A SUB PANEL. RUN NEW SERVICE ENTRANCE CONDUIT, USE MOGUL LB'S WHERE NEEDED (INSIDE AND OUTSIDE). PULL NEW SERVICE CONDUCTORS DIRECTLY TO THE NEW PANEL. METER SOCKET WITH 100A METER/MAIN SOCKET U7375-RL-KK-CECHA - MILBANK (METER-MAIN IS NOW THE PRIMARY GROUND/BONDING POINT) REPLACE MAIN SERVICE PANEL WITH A 100/100A PANEL MINIMUM 30 BREAKER SLOTS, MOVE NEW MAIN SERVICE PANEL TO A CODE COMPLIANT LOCATION. RECOMMENDED INTERCONNECTION BE THROUGH NEW MILLBANK METER LUGS ONCE ALL WORK COMPLETED.