Chicago · permit B100913130
2332 N KILPATRICK AVE
ESC: NEEDED PRE-ESC: NOT ALLOWED BFEED REQ'D: 20A RECOMMENDED INTERCON: SUPPLY TAP IN THE MAIN SERVICE PANEL MATER AND MSP LOCATION CODE VIOLATIONS _______________ METER/SERVICE: SOCKET/OVERHEAD LOOKS LIKE IT IS LOCATED IN A STAIRWELL PANEL: 125/100A NEEDS MOVED SCOPE REPLACE METER SOCKET WITH 100A METER/MAIN SOCKET U7375-RL-KK-CECHA - MILBANK MOVE TO A CODE COMPLIANT LOCATION NEW RISER MAY NEED NEW MAST - CHECK HEIGHT OF OVERHEAD CABLES MOVE EXISTING MAIN SERVICE PANEL TO A CODE COMPLIANT LOCATION. INSTALL A J-BOX WHERE THE OLD PANEL USED TO BE AND SPLICE BRANCH CIRCUITS THEN RE-DIRECT THEM TO NEW PANEL (USE OF FLEX IS ALLOWED INSIDE THE WALLS. RUN NEW SERVICE ENTRANCE CONDUIT, USE MOGUL LB'S WHERE NEEDED (INSIDE AND OUTSIDE). PULL NEW SERVICE CONDUCTORS DIRECTLY TO THE NEW PANEL. ENSURE BONDING AND GROUNDING ARE UP TO CODE. BOND THE COLD WATER MAIN. BOND STREET SIDE FIRST AHJ: CHICAGO GOVERNING ELECTRICAL CODE: 2018 CHICAGO ELECTRICAL CODE CHECK AND FOLLOW AHJ AMENDMENTS PRIOR T
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2021-03-17
- Issued
- 2021-03-17
- Time to issue
- same day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- VIVINT SOLAR DEVELOPER,LLC,
Chicago details
- Review type
- EXPRESS PERMIT PROGRAM
- Milestone
- COMPLETE
- Community area (code)
- 19