2407 S LAWNDALE AVE

ESC: NEEDED PRE-ESC: NOT ALLOWED BFEED REQ'D: 40A METER/SERVICE: SOCKET/OVERHEAD PANEL: 100/100 RECOMMENDED INTERCON: SUPPLY TAP IN THE METER CAN MAIN SERVICE IS BEHIND A CABINET DOOR; DEADFRONT AND COVER ARE MISSING. SCOPE REPLACE MAIN SERVICE PANEL WITH A 125/100 MAIN (MINIMUM 24 BREAKER SLOTS) HOM2448M125PRB ENSURE BONDING AND GROUNDING ARE UP TO CODE. BOND THE COLD WATER MAIN. BOND STREET SIDE FIRST