Chicago · permit B100894588
2948 N MAJOR AVE
ESC: NEEDED PRE-ESC: POST INSTALL BFEED REQ'D: 20A METER/SERVICE: SOCKET/OVERHEAD PANEL: EATON/CHALLENGER 100/100A RECOMMENDED INTERCON: SUPPLY TAP CUSTOMER WILL NEED TO MOVE THE CLOTHES DRYER THAT IS IN FRONT OF THE MAIN ELECTRICAL PANEL PRIOR TO INSPECTION. TANDEM BREAKERS (NOT ALLOWED PER CHICAGO CODE) BREAKER USED NOT SPECIFIED BY THE MANUFACTURER (SQUARE D) PANEL ONLY RATED FOR 1 BRANCH CIRCUITS WHEN MAIN BREAKER USED. NUMEROUS BREAKERS ARE DOUBLE TAPPED. (20 TOTAL BRANCH CIRCUITS) SCOPE REPLACE 100A METER SOCKET WITH A COMED APPROVED 100A METER SOCKET AND PAN. UPGRADE MAIN ELECTRICAL PANEL TO A 125/100A (24 BREAKER POSITION MINIMUM) SUGGESTED PANEL HOM2448M125PRB ENSURE BONDING AND GROUNDING ARE UP TO CODE. BOND THE COLD WATER MAIN. AHJ CHICAGO GOVERNING ELECTRICAL CODE 2018 CHICAGO ELECTRICAL CODE