Chicago · permit B100893536
5515 S FAIRFIELD AVE
REPLACE DUAL ENCLOSED METER SOCKETS WITH COMED APPROVED NEW DUAL 100A METER SOCKET AND PAN. REPLACE RISER AND SERVICE ENTRANCE CABLES (PROPERLY SIZED) THE INTERCONNECTION FOR SOLAR WILL NEED TO BE REDONE. INSTALL GROUND BUSINGS IN METER SOCKETS AND IN MAIN SERVICE PANEL. FOR THE MAIN SERVICE ENTRANCE AND FOR THE SOLAR TIE IN CONDUIT. THE MAIN SERVICE PANEL IS A SIEMENS S2020B1100 - INSTALL A GROUND BAR AND BOND WITH THE NEUTRAL BAR LAND THE MAIN SERVICE NEUTRAL ON THE NEUTRAL BAR AND LAND THE SOLAR NEUTRAL ON THE NEUTRAL BAR. THE SOLAR DISCONNECT NEEDS TO BE CHANGED TO A FUSED TYPE AND MOVED TO WITHIN 5 FEET OF THE MAIN SERVICE PANEL. RMC MUST BE USED BETWEEN THE DISCONNECT AND THE MAIN SERVICE PANEL. GO THROUGH THE MAIN SERVICE PANEL. FOR ANY BRANCH CIRCUITS USING #14 OR SMALLER WE NEED TO DERATE THE BREAKERS TO 15A.
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE