Chicago · permit B100889075

3037 W 38TH ST

THERE IS A 20A BREAKER WITH 14 AWG THAT NEEDS TO BE SWAPPED FOR A 15A BREAKER. A COLD WATER GROUND NEEDS TO BE RAN, AND A GROUND ROD NEEDS TO BE ADDED

Permit

Permit type
PERMIT – EXPRESS PERMIT PROGRAM
Class
Unknown
Trade
Electrical
Nature of work
Other
Work
Electrical Work
Status
COMPLETE

Location

City
Chicago
State
IL

Dates

Applied
2020-08-28
Issued
2020-08-28
Time to issue
same day

Chicago details

Review type
EXPRESS PERMIT PROGRAM
Milestone
COMPLETE
Community area (code)
58

Data as of 2026-09-21.