Chicago · permit B100870288

2244 S WESTERN AVE

SECURE ALL RACEWAYS IN ELECTRICAL ROOM. - INSTALL STRUT STRAPS ON CONDUITS THAT HAVE NONE. - SECURE STRUT TO WALL ABOVE MDP. - INSTALL SUPPORTS FOR CONDUITS THAT HAVE NONE. - REMOVE UNUSED ELECTRICAL IN ELECTRIC ROOM. - REMOVE PIPE COMING DOWN WALL WITH EXPOSED WIRING. - FURNISH AND INSTALL 1 X GROUND FAULT DETECTION SYSTEM IN ELECTRIC ROOM IN ACCORDANCE WITH CEC 250.21 (B)(1) AND 250.21 (B)(2). - LABEL MAIN SERVICE DISCONNECT AND METER IN ACCORDANCE WITH CEC 250.21 (C) 'CAUTION: UNGROUNDED SYSTEM OPERATING - 480 VOLTS BETWEEN CONDUCTORS'.

Permit

Permit type
PERMIT – EXPRESS PERMIT PROGRAM
Class
Unknown
Trade
Electrical
Nature of work
Other
Work
Electrical Work
Status
COMPLETE

Location

City
Chicago
State
IL

Dates

Applied
2020-04-09
Issued
2020-04-09
Time to issue
same day

Chicago details

Review type
EXPRESS PERMIT PROGRAM
Milestone
COMPLETE
Community area (code)
31

Data as of 2026-09-21.

Other permits issued in Chicago, April 2020