Chicago · permit B100870288
2244 S WESTERN AVE
SECURE ALL RACEWAYS IN ELECTRICAL ROOM. - INSTALL STRUT STRAPS ON CONDUITS THAT HAVE NONE. - SECURE STRUT TO WALL ABOVE MDP. - INSTALL SUPPORTS FOR CONDUITS THAT HAVE NONE. - REMOVE UNUSED ELECTRICAL IN ELECTRIC ROOM. - REMOVE PIPE COMING DOWN WALL WITH EXPOSED WIRING. - FURNISH AND INSTALL 1 X GROUND FAULT DETECTION SYSTEM IN ELECTRIC ROOM IN ACCORDANCE WITH CEC 250.21 (B)(1) AND 250.21 (B)(2). - LABEL MAIN SERVICE DISCONNECT AND METER IN ACCORDANCE WITH CEC 250.21 (C) 'CAUTION: UNGROUNDED SYSTEM OPERATING - 480 VOLTS BETWEEN CONDUCTORS'.
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2020-04-09
- Issued
- 2020-04-09
- Time to issue
- same day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- WILLCOX ELECTRICAL INC.
Chicago details
- Review type
- EXPRESS PERMIT PROGRAM
- Milestone
- COMPLETE
- Community area (code)
- 31