Chicago · permit B100839815

1500 S INDIANA AVE

SCOPE OF WORK: ELECTRICAL INSTALLATION REQUIREMENTS FOR NEW AND REPLACEMENT HVAC EQUIPMENT. EQUIPMENT POWER REQUIREMENTS: 208VOLT, 3-PHASE AS LISTED BELOW. REPLACEMENT AIR HANDLING UNIT: MCA 36 AMPS (FED FROM PENTHOUSE PANEL RDPN, EXISTING CIRCUIT ON ROOF) REPLACEMENT 5KW SPACE HEATER #1: MCA 14 AMPS (FED FROM PENTHOUSE PANEL RDPN) REPLACEMENT 5KW SPACE HEATER #2: MCA 14 AMPS (FED FROM PENTHOUSE PANEL EFP) NEW CONDENSER UNIT: MCA 245 AMPS MOCP 250AMPS ¿ UNIT SUPPLIED WITH FACTORY MOUNTED MAIN DISCONNECT. A) (1) 400AMP, 3-POLE, FUSED VACU-BREAK SWITCH INSTALLED INTO EXISTING 600AMP DISTRIBUTION PANEL, (MD) SOUTH WALL MAIN ELECTRIC ROOM 1ST FLOOR. (ITE V7H3205) INCLUDING (3) 250AMP FUSES. B) (1) 208V, 250AMP, 3-PHASE, 3-WIRE PLUS EQUIPMENT GROUND CIRCUIT RUN FROM NEW SWITCH TO ROOF TOP CONDENSER UNIT CONSISTING OF (2) 1-1/2" CONDUITS WITH (3) 1/0 + (1) #4 GROUND IN EACH. C) (1) EMPTY ¾¿ CONTROL CONDUIT INSTALLED FROM 1ST FLOOR ELECTRIC ROOM TO PENTHOUSE. D) REQUIRED CONDUIT, WIRING AN

Permit

Permit type
PERMIT – EXPRESS PERMIT PROGRAM
Class
Unknown
Trade
Electrical
Nature of work
Other
Work
Electrical Work
Status
COMPLETE

Location

City
Chicago
State
IL

Dates

Applied
2019-09-09
Issued
2019-09-09
Time to issue
same day

Value and contractor

Declared value
Log in with your free account
Total fee
Log in with your free account
Contractor
MKD ELECTRIC, INC.

Chicago details

Review type
EXPRESS PERMIT PROGRAM
Milestone
COMPLETE
Community area (code)
33

Data as of 2026-09-21.