Chicago · permit B100782992
3344 W CERMAK RD
ATT IL1266 DECOMM: UMTS 1900, CAP-OFF. LTE-6C, FNET, P2: RELOCATE 700 RRU FROM P2 TO P4; ADD RRUS 4478 B14 (4T/4R), CONNECT (2) LOW BAND PORTS ON P2 + (2) LOW BAND PORTS ON P1.RRU SWAP, PCS (1900), P4: SWAP RRU FOR RRUS 4415 B25 (4T/4R). BWE: NO TOWER WORK. LTE-6C: INSTALL (3)25 AMP BREAKERS, PCS SWAP: GPS SPLITTER KIT, UPPER/LOWER FIBERS, SFPS, POLE MOUNTS, SWAP (2) DUS-41 FOR (2) 5216, FINAL BBU CONFIGURATION: (2) 5216 + (2) XMU AND IDLE CABLE, SWAP POWER PLANT FOR 7100 WITH 13 RECTIFIERS AND 4 CONVERTERS AND 8 STRINGS OF BATTERIES, 5 STRINGS IN THE BATTERY RACK, 3 UNDER POWER PLANT SHELVES.
Permit
- Permit type
- PERMIT – EXPRESS PERMIT PROGRAM
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- Other
- Work
- Electrical Work
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2018-09-13
- Issued
- 2018-09-13
- Time to issue
- same day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- Individual
Chicago details
- Review type
- EXPRESS PERMIT PROGRAM
- Milestone
- COMPLETE
- Community area (code)
- 30