Chicago · permit 100939777
6160 N CICERO AVE
REMOVE AND REPLACE EXISTING ; MOVE WCS RRUS32 FROM POS2 TO POS1, REPLACE HEX AT POS2 WITH AIR6449 N77 ; EXISTING: (6) 8AWG DC TRUNKS, (2) DC6-48-60-18-8C-EV (LOCATED AT GAMMA AT THE PLATFORM) , (1) DC6-48-60-0-8C-EV (LOCATED AT GAMMA AT THE PLATFORM), (9) DC2-48-60-0-9E (3 PER SECTOR), (1) 12 PAIR FIBER TRUNK, (1) 18 PAIR FIBER TRUNK ; REMOVE: (6) 8AWG DC TRUNKS, (2) DC6-48-60-18-8C-EV (LOCATED AT GAMMA AT THE PLATFORM), (1) DC6-48-60-0-8C-EV (LOCATED AT GAMMA AT THE PLATFORM), (9) DC2-48-60-0-9E (3 PER SECTOR), (1) 12 PAIR FIBER TRUNK, (1) 18 PAIR FIBER TRUNK ; INSTALL: (3) DC9-48-60-24-PC16-EV, (9) 6AWG DC TRUNK, (3) 24 PAIR FIBER TRUNK EXISTING PP ALPHA TE41 - REPLACE WITH VERTIV 512 10R / 0C - REUSE EXISTING BATTERIES, EXISTING (1) DC6-48-60-RM IN DC POWER PLANT - REMOVE EXISTING (1) DC12-48-60-0-25E, ADD (1) DC12-48-60-0-25E TO REPLACE THE INDOOR (1) IN THE OLD DCPP, NO DC UPCONVERTERS WILL BE REQUIRED DUE TO THE DC CABLE LENGTHS, NO GENERATOR, INSTALL #6 TELCOFLEX FROM PP TO R
Permit
- Permit type
- PERMIT - NEW CONSTRUCTION
- Class
- Unknown
- Trade
- Electrical
- Nature of work
- New
- Status
- COMPLETE
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2021-09-22
- Issued
- 2021-09-22
- Time to issue
- same day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- MASTEC NETWORK SOLUTIONS LLC
Chicago details
- Review type
- STANDARD PLAN REVIEW
- Milestone
- COMPLETE
- Community area (code)
- 12