Preview 887,040 permits — every permit Chicago, Austin and Seattle issued in the last ten years. The full load is in progress, so this is how far it has got. Sourced from city open-data portals. Data as of 2026-09-21.

Chicago · permit 100934374

4608 W BELMONT AVE

"|| REMOVE P1 AND P2 ANTENNASRELOCATE UMTS 850 RRU FROM P1 TO P4 AND COMBINE WITH FNET USING TWIN DIPLEXERCBC78T-DS-43.RELOCATE P3 NNH4-65B-R6 ANTENNA TO P1 AND RECONNECT WCS TO ITREPLUMB PCS FROM P2 TO THE RELOCATED ANTENNA IN P1INSTALL 4449 B5/B12 IN P1REMOVE 700 B12 RRUS11 AND 850 B5 4478REPLUMB THE 4 JUMPERS FROM THE 8843 RADIO THAT WERE CONNECTED TO P3 SO THATTHEY ARE ON P4.INSTALL C-BAND AIR6449 AAS WITH 2 FIBER AND 1 POWER IN MIDDLE OF SECTOR FACE WITH 3'SPACING ON EITHER SIDENO NEW SQUIDS OR TRUNKSINSTALL (2) NEW OUTDOOR DC 12 BOXES ON THE H-FRAME/ ICE BRIDGE WITH THE EXISTINGOUTDOR DC12PULL (8) EXISTING POWER TRUNKS OUT OF THE POWER PLANT AND RETERMINATE THEM TOTHE NEW DC12'SREPLACE EXISTING ARGUS TE41 POWER PLANT WITH NEW EMERSON 512REPLACE BATTERY CABINET BUT REUSE EXISTING BATTERIESINSTALL BREAKERS FOR NEW RADIOS AND AIR ANTENNAS. NO UPCONVERTERS ARE NEEDEDDUE TO TRUNK BEING UNDER 150'

Permit

Permit type
PERMIT - NEW CONSTRUCTION
Class
Unknown
Trade
Electrical
Nature of work
New
Status
COMPLETE

Location

City
Chicago
State
IL

Dates

Applied
2021-09-13
Issued
2021-09-13
Time to issue
same day

Chicago details

Review type
STANDARD PLAN REVIEW
Milestone
COMPLETE
Community area (code)
15

Data as of 2026-09-20.