Chicago · permit 100688809
4425 N SEELEY AVE
EXISTING MOTOR FAILED CATEGORY 5 TESTING BECAUSE IT WAS UNABLE TO PICK THE 1200LB.RATED CAPACITY LOAD REMOVE EXISTING MOTOR BRING TO MACHINE SHOP TO EITHER REPAIR OR IF NEEDEED, REPLACE WITH NEW MOTOR. SCHEDULE RE-INSPECTION, PERFORM CATEGORY 5 FULL LOAD GOVERNOR TEST WITH CITY OF CHICAGO INSPECTOR. PURSUANT TO THE SCOPE OF WORK SUBMITTED. EV006007
Permit
- Permit type
- PERMIT - ELEVATOR EQUIPMENT
- Class
- Unknown
- Trade
- Elevator
- Nature of work
- Other
Location
- City
- Chicago
- State
- IL
Dates
- Applied
- 2017-02-01
- Issued
- 2017-02-01
- Time to issue
- same day
Value and contractor
- Declared value
- Log in with your free account
- Total fee
- Log in with your free account
- Contractor
- ELEVATOR INDUSTRIES OF IL
Chicago details
- Review type
- CONVEYANCE DEVICE PERMIT
- Community area (code)
- 4